Added monthly inspection instructions

This commit is contained in:
Kenneth John Odle 2026-10-21 13:45:01 -04:00
parent 50cf260a5d
commit 36855d8071

View File

@ -7,6 +7,7 @@
\usepackage[left=1cm,right=1cm,top=1cm,bottom=1cm]{geometry}
\usepackage{tabularray}
\usepackage{ninecolors}
\usepackage{enumitem}
\usepackage{wasysym}
\usepackage{multicol}
\setlength{\columnsep}{2cm}
@ -55,6 +56,42 @@ Date & By & Pressure & Weight & Condition \\
\vspace{8mm}
}
\newcommand{\kpro}{
\vspace{8mm}
\begin{quote}
\begin{center}
MONTHLY VISUAL INSPECTION
\end{center}
{\fontsize{7}{8} \selectfont
Fire extinguisher inspectiongs should be performed upon initial placement into service and at regular periodic intervals not to exceed 31 days.
\textbf{Visual Inspection Instructions:}
\begin{enumerate}[noitemsep]
\item Ensure the fire extinguisher is visible and access is unobstructed.
\item Ensure the fire extinghuisher is properly mounted and secure.
\item Ensure the front nameplate operating instructions face outward and are legible. Relocate extinguisher or clean nameplate as required.
\end{enumerate}
\textit{(Correct and resolve any discrepancies observed in the first three steps.)}
\begin{enumerate}[noitemsep,resume]
\item Ensure pull-pin and/or original visual inspection tamper seal is installed and still intact.
\item Ensure pressure gauge needle reads within green operable area.
\item Ensure the discharge nozzle and/or hose assembly is unobstructed and securely attached.
\item Closely examine all external extinguisher components for any signs of damage, impact, wear, leakage, or corrosion.
\item Heft or weigh fire extinguisher to ensure it is properly charged. Total charged extinguisher weight (gross weight) is indicated on the product label/nameplace.
\item Date and initial fire exitnguisher inspection tag.
\end{enumerate}
\textbf{Note:} Any time an equipment related discrepancy described in steps 4 through 8 is observed during an inspection procedure, the fire extinguisher must be discarded and replaced.
\textbf{Note:} Annual maintenance requirements include verification of the fire extinguisher weight at least annually and that the the year of manufacture stamped on the bottom of the cylinder is within the desginated 12-year maximum shelf life.
} % end selectfont
\end{quote}
}
\begin{document}
\pagestyle{empty}
\sffamily
@ -71,5 +108,18 @@ Date & By & Pressure & Weight & Condition \\
\end{multicols}
\end{document}
\newpage
\newgeometry{left=1cm,right=1cm,top=2cm,bottom=1cm}
\begin{multicols}{2}
\kpro
\kpro
\kpro
\kpro
\end{multicols}